معرفی
تامین کننده
جزيیات
خانه/ ترانسمیتر/ ترانسمیتر دما/ Yokogawa/ YTA610-JA1A4DN/KU2/C3 | Yokogawa YTA610 Temperature Transmitter

YTA610-JA1A4DN/KU2/C3 | Yokogawa YTA610 Temperature Transmitter
قیمت حدودی:
78,850,000 تومان
به دلیل سفارشی بودن کالاها و نوسانات قیمت ارز، قیمتها حدودی بوده. لطفا برای اطلاع از قیمت بروز کالا استعلام بگیرید.
تامین کننده

یاران صنعت فجر
ارسال به سراسر کشور
ضمانت اصالت و سلامت فیزیکی کالا
در مورد این محصول
ویژگی ها / Specifications
A | Always A |
/C3 | NAMUR NE43 compliant? |
KU2 | ATEX |
Model | YTA610 - Temperature Transmitter |
Enclosure | IP66/IP67 |
Certificate | KEMA 07ATEX0130 |
Housing code | A - Aluminium |
Sensor input | 1 - Single |
Output signal | -J - 4 to 20 mA DC with digital communication HART 7 protocol |
Sensor circuit | Uo=6V, Io=90mA, Po=135mW, Co=10?F, Lo=3.9mH |
Electrical code | 4 - M20 female |
Mounting bracket | N - None |
Integral indicator | D - Digital indicator with Local Operating Switch |
Ambient Temperature | -40 to 70?C for T4, -40 to 50?C for T5 |
Dielectric strength | 500 V a.c.r.m.s., 1 min |
Output signal limits | 3.8 mA to 20.5 mA |
Electrical Connection | 1/2 NPT female and M20 female? |
Supply/Output circuit | Ui=30V, li=200mA, Pi=1.0W, Ci-22nF, Li=0mH |
Failure alarm up-scale | output status at CPU failure and hardware error is 110%, 21.6 mA or more. |
In this case Sensor burnout is High | 110%, 21.6 mA DC. |
Ambient Temperature for Gas Atmospheres | -40 to 75?C for T6, -40 to 80?C for T5 |
Ambient Temperature for Dust Atmospheres | -30 to 65?C for T70?C, -30 to 80?C for T90?C |
Description / توضیحات
Model and Suffix Codes
Option Codes:
4-20 mA:
[Intrinsically safe approval]
Applicable Standard: EN 60079-0; 2012+A11:2013, EN 60079-11:2012
Certificate No. FM16ATEX0019X
II 1 G Ex ia IIC T5...T4 Ga
Entity Parameters:
[+, -, C, 1, 2, 3, 4, 5] to Earth terminal
[+, -, C] to [1, 2, 3, 4, 5]
[Flameproof and Dust Ignition Proof Approval]
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014
II 2 G Ex db IIC T6/T5 Gb, II 2 D Ex IIIC T70?C/T90?C Db
NOTE:
Applicable for Electrical Connection Code 2 and 4.
Not applicable for Fieldbus type.
محصولات مشابه
ارسال به سراسر کشور
ضمانت اصالت و سلامت فیزیکی کالا
زمان تحویل:14 هفته
برای تکمیل استعلام به سبد استعلام مراجعه کنید.
در مورد این محصول