Features
- CO2 range:
- 0 to 2000 ppm
- 0 to 5000 ppm
- 10 to 90% RH range
- -4 to 140°F (-20 to 60°C) temp range
- ±(50ppm 2%/3%) CO2 accuracy
- Humidity accuracy:
- ±3 % RH (30 to 70% RH)
- ±5 % (10 to 90% RH)
- CO2 auto calibration
- BACnet, Modbus or analogue outputs
- Temperature compensation
- Highly insensitive to pollution
- Snap-on enclosure
The E+E EE800 CO2 / Temperature / RH Transmitter accurately measures CO2, temperature and relative humidity in HVAC applications. The EE800 also calculates the dew point temperature. The EE800 incorporates the E+E dual wavelength NDIR CO2 sensor, which compensates for aging effects, is highly insensitive to pollution and offers outstanding long term stability. A multiple point CO2 and temperature factory adjustment procedure leads to excellent CO2 measurement accuracy over the entire temperature working range. Applications for the EE800 include: Demand controlled ventilation Heating, ventilation and air conditioning Building management